Skip to content
5

Generator load test

INS-2208 · Fallowmere House · Jan 14, 2027 · Doug Pettibone

Checklist · 5 items

  • Fuel
    Fuel level at or above three-quarters
    Pass
  • Battery
    Battery and charger normal
    Pass
  • Transfer
    Transfer time 10 seconds or less
    Transfer took 14 seconds on two attempts.
    Corrective action CA-305
    Fail
  • Run
    30-minute run under building load
    Pass
  • Log
    Test log signed
    Pass

Summary

Status
Completed
Score
80% (4 of 5 passed)
Started
Jan 14, 10:00 AM
Completed
Jan 14, 11:10 AM
Inspector
Doug Pettibone

Corrective actions (1)